506. Cable couplers on circuits operating at voltages higher than 300 V shall be:
(1)  of a type designed for the cables on which they are used;
(2)  of a design and dimensions suitable for the worst conditions under which they are used;
(3)  equipped with covering, hoods or seals to cover the unprotected ends when they are disconnected;
(4)  equipped with cable clamps and gaskets on the joints to prevent any infiltration of water;
(5)  designed so that they comply with one of the following requirements designed to prevent accidental disconnection when they are energized:
(a)  special tools shall be used to separate the sections;
(b)  the sections shall be held together by a padlock;
(c)  a control circuit shall be included and shall trip the cable circuit breaker to de-energize the phase terminals before separating them.